ZW20-12F Primary and secondary fusion outdoor high voltage vacuum circuit breaker
Overview:
The ZW32C-12 Outdoor High Voltage Vacuum Circuit Breaker adopts vacuum arc extinguishing technology, equipped with a permanent magnet operating mechanism (spring mechanism). It integrates micro-processing technology, modern network communication technology, and new switch manufacturing materials. With a rated voltage of 12kV and a frequency of 50Hz, this circuit breaker is suitable for three-phase AC outdoor power distribution systems. It is widely used in urban power grids as a sectionalizing or interconnection switch or in rural power distribution systems as an outdoor substation outlet switch. The ZW32C-12 breaker effectively replaces traditional reclosers, handling the breaking and making of load current and short-circuit current.
Application Range:
The ZW32C-12 Outdoor High Voltage Vacuum Circuit Breaker is suitable for various grid applications, including:
•Sectionalizing or interconnection switch in urban power grids
•Protection and control in rural power distribution systems
•Outlet switch in outdoor substations
Technical Requirements:
1.Rated Voltage: 12kV
2.Frequency: 50Hz
3.Ambient Temperature: -40ºC to +55ºC, daily temperature variation not exceeding 25K
4.Altitude: Not exceeding 2000m
5.Wind Speed: Not exceeding 35m/s
6.Pollution Level: Grade IV
7.Installation Location: Free from inflammable, explosive hazards, and chemical corrosion
8.Seismic Intensity: Not exceeding 8 degrees
Precautions:
1.The breaker should be installed in an environment free from severe vibrations and impacts, away from chemically corrosive substances.
2.Regular inspection and maintenance should be performed to ensure normal operation and long service life.
3.Follow the operating procedures strictly to ensure the safety of personnel and equipment.
Serial number | project | unit | data | ||
1 | Rated voltage | kV | 12 | ||
2 | Rated frequency | Hz | 50 | ||
3 | Rated current | A | 630 | 1000 | |
4 | Rated short circuit breaking current | kA | 20 | 25 | |
5 | Rated peak tolerance current | kA | 50 | 63 | |
6 | Rated short-time tolerance current | kA | 20 | 25 | |
7 | Rated short circuit closing current | kA | 50 | 63 | |
8 | Rated operating sequence | 0-0.3S-CO-180S-CO | |||
9 | Mechanical life | cycles | 10000 | ||
10 | Rated current breaking times | cycles | 10000 | ||
11 | Rated shortcircuit breaking number | cycles | 30 | ||
12 | Power frequency withstand voltage I min | Alterating (wet) to the ground | kV | 34 | |
Alternate (dry), ground / fracture | kV | 42/48 | |||
13 | Lightning impulse tolerance voltage | Interphase, ground/fracture | kV | 75/85 | |
14 | Secondary circuit 1min power frequency withstand voltage | V | 2000 | ||
15 | quality | kg | about140 | ||
16 | Contact pitch | mm | 8.5-10 | ||
17 | Contact contact stroke | mm | 2.5-4 | ||
18 | Average breakout speed | m/s | 1.2±0.2 |