ZN85-40.5 Indoor High Voltage Vacuum Circuit Breaker
Operating Environment
The ZN85-40.5 series indoor high voltage vacuum circuit breaker is suitable for use in three-phase AC 50Hz power systems with a rated voltage of 40.5kV. It is designed for industrial and mining enterprises, power plants, and substations, where it is used for switching load currents, overload currents, and fault currents. The unique vertical arrangement of the circuit breaker reduces its depth, making the overall layout more rational, aesthetically pleasing, and compact. It is ideal for indoor environments with temperatures ranging from -10ºC to 40ºC and altitudes up to 1000 meters. The breaker can operate reliably in humidity levels up to 95% and withstand earthquake intensities up to level 8.
Application Scope
The ZN85-40.5 circuit breaker is widely used in high-voltage power transmission settings, particularly in applications requiring frequent operations, such as power dispatch centers and industrial manufacturing facilities. The breaker's composite insulation structure, featuring three-phase arc extinguishing chambers and electrically connected components isolated by independent epoxy resin insulating tubes, meets the necessary air and creepage distance requirements under normal operating conditions. The main conductive circuit's vacuum interrupter and the moving and stationary conductive connections are installed within the insulating tube, reducing the phase spacing to just 300mm, thereby minimizing the device's size while enhancing the reliability of the electrical connections through fixed connections. The device's compact design and maintenance-free spring operating mechanism ensure flexible operation and extended service life.
Precautions
When using the ZN85-40.5 series vacuum circuit breaker, it is essential to ensure that the installation environment meets the specified operating conditions. Avoid using the equipment in environments outside the recommended temperature or humidity ranges and keep it away from potential hazards such as fire, explosion, or chemical corrosion. Given the circuit breaker's compact structure, care should be taken during installation and maintenance to prevent damage to its precise components. For settings involving frequent operations, regular inspections are necessary to ensure continued high reliability and performance.
Technical Specification | |||
1 | Rated voltage | kV | 40.5 |
2 | 1min Power frequency withstand voltage(effective value) | kV | 95 |
3 | Lightning impulse withstand voltage (peak value) | kV | 185 |
4 | Rated frequency | Hz | 50 |
5 | Rated current | A | 125,160,200,250 |
6 | Rated short-time withstand current | kA | 25,31.5 |
7 | Rated peak withstand current | kA | 63,80 |
8 | Rated short circuit duration | s | 4 |
9 | Rated short-circuit breaking current | kA | 25,31.5 |
10 | Rated short-circuit making current | kA | 63,80 |
11 | Rated operating sequence | 0-0.3S-CO-180S-CO | |
12 | Breaking time | ms | <80 |
13 | Rated short-circuit breaking current times | cycles | 20 |
14 | Single capacitor bank breaking current | A | 630 |
15 | Back-to-back capacitor bank breaking current | A | 400 |
16 | Rated operating voltage | V | AC110,220;DC110,220 |
17 | Mechanism Endurance | cycles | 10000 |