Manufactured from: Polyolefin, inner coated with hot-melt adhesive.
Purpose: Providing fast and permanent repair and sealing protection for power cables.
Features: High tensile strength, abrasion, and corrosion resistance.
Installation: A corrosion-proof metal channel is used to close the sleeve duringinstallation.
Shrink temperature: Starts at 90°C, fully recovers at 130°C.
Selection Table:
Spec. |
As Supplied(mm) |
After Recovered |
Width(W)Min Wall Thickness(±0.3) |
Width(W)Max Wall Thickness(±0.3) |
ALRSXP-30/12 |
120 |
1.3 |
38 |
3.8 |
ALRSXP-40/12 |
130 |
1.2 |
38 |
3.8 |
ALRSXP-50/17 |
160 |
1.3 |
53 |
3.8 |
ALRSXP-65/24 |
205 |
1.2 |
75 |
3.8 |
ALRSXP-85/27 |
270 |
1.3 |
82 |
3.8 |
ALRSXP-100/27 |
320 |
1.4 |
82 |
3.8 |
ALRSXP-120/40 |
380 |
1.4 |
129 |
3.8 |
ALRSXP-150/50 |
475 |
1.4 |
157 |
3.8 |
ALRSXP-160/50 |
505 |
1.3 |
157 |
3.8 |
ALRSXP-170/51 |
535 |
1.2 |
160 |
3.8 |
ALRSXP-180/51 |
565 |
1.1 |
160 |
3.8 |
ALRSXP-195/52 |
590 |
1.0 |
163 |
3.8 |
Property |
Test Method |
Standard Value |
Tensile Strength |
ASTM-D-638 |
≥12MPa |
Elongation at Break |
ASTM-D-638 |
≥300% |
Changes in Tensile Breaking Strength After Heat Aging |
ASTM-D-5510 |
≤+20% |
Dielectric Strength |
IEC 60243 |
≥15kV/mm |
Volume Resistivity |
IEC 60093 |
≥1x1013Ωcm |
Heat Shock |
160°C,4h |
No Crack |
Water Absorption |
ISO 62 |
≤0.1% |
Hardness(Shore A) |
IS0 868 |
≥80 |
Longitudinal Shrinkage |
ASTM-D-2671 |
≤10% |
Brittle Temperature |
IS0 974 |
-40°C |
Eccentricity |
ASTM-D-2671 |
≤30% |