Spec. | As Supplied(mm) | After Recovered | ||
Inner Diameter Min | Wall Thickness(±0.3) | Inner Diameter Max | Wall Thickness(T:±0.3) | |
ALRSJG-30/12 | 30 | 1 | 12 | 2.2 |
ALRSJG-35/14 | 35 | 1 | 14 | 2.3 |
ALRSJG-40/17 | 40 | 1 | 17 | 2.3 |
ALRSJG-50/22 | 50 | 1 | 22 | 2.5 |
ALRSJG-35/13 | 35 | 1.2 | 13 | 3 |
ALRSJG-40/15 | 40 | 1.2 | 15 | 3 |
ALRSJG-50/19 | 50 | 1.1 | 19 | 3 |
ALRSJG-55/24 | 55 | 1.4 | 24 | 3.2 |
ALRSJG-60/26 | 60 | 1.4 | 26 | 3.2 |
ALRSJG-70/29 | 70 | 1.4 | 29 | 3.2 |
ALRSJG-75/35 | 75 | 1.5 | 35 | 3.2 |
ALRSJG-80/36 | 80 | 1.4 | 36 | 3.2 |
ALRSJG-90/41 | 90 | 1.6 | 41 | 3.5 |
ALRSJG-100/45 | 100 | 1.5 | 45 | 3.5 |
Property | Test Method | Standard Value |
Tensile Strength | ASTM-D-638 | ≥8MPa |
Elongation at Break | ASTM-D-638 | ≥300% |
Changes in Tensile Breaking Strength After Heat Aging | ASTM-D-5510 | ≤±30% |
Volume Resistivity | IEC 60093 | ≥1x1014Ω.cm |
Dielectric Strength | IEC 60243 | ≥20kV/mm |
Tracking Resistance | IEC 60587 | 1A 3.5 |
Dielectric Constant | IEC 60250 | ≤5 |
Heat Shock | 160ºC,4h | No Crack |
Water Absorption | ISO 62 | ≤0.1% |
Hardness(Shore A) | ISO 868 | ≥80 |
Brittle Temperature | ISO 974 | -40ºC |