1KV 3-cores heat shrinkable termination kits/heat shrinkable termination kit, cable accessories
Material: XLPE
Usable: 1KV cable
Hardness: 80(Shoea A)
Tensile strength: 12Mpa
Elongation at break: 300%
Dielectric strength: More than 20KV/mm
AC voltage withstand: 2.5kv
Shrink temperature: 120-140
Shrink ration(dia): 250%
Longitudinal shrinkage: ± 5%
What's the difference between Heat Shrink and Cold Shrink?
Heat Shrink products offers a range of wall thicknesses and adhesive options that can be better tailored to your application, offering precise shrink ratios.
No tools are required with our Cold Shrink products, speeding up your installation time. Reduces chances of cable damage, since there is no heating element. The cold shrink technology is more versatile since there are no need for permits, and is safe for enclosed spaces.
Features
• Power Cable Termination Technology: Stress Cone
• Power Cable Termination Voltage Class(kV): ≤ 42
• Cable Shield Style: Copper wire, copper tape
• Number of Cores: 1, 3
• Application Type: Indoor
• Industry Standards: Design Specification GB/T 12706.4, IEC 60502-4
Characteristics
• Easy/convenient installation: Stress cone wholly composed inside the silicone rubber body greatly releases the electric stress at the screen cut edge. Pre-expanding with removable plastic spiral tube inside, the elastic silicone rubber body will shrink automatically and tightly onto the needed position by removing the plastic spiral tube without heating or special tools.
• Reliable insulation: Adopting Germany liquid silicone rubber, serving the utilities and industry successfully for 20 years.
• Superior moisture sealing: Triplex sealing design and hydrophobic performance of silicone rubber ensure environmental stability.
• Safety for installing fault: Considerate design reduces the incidence of installing faults which likely occur.
• Wide usage: Possessing a series of superior performances, the cold shrink accessories can be widely used in various regions, especially fire forbidden area, high sea level, cold weather, high-humidity, salt-fog and heavy polluted regions.
Specification
Voltage |
Cable cores |
Cable conductor size (mm2) |
Suitable insulation dia. range (mm) |
12/20(24)kV and below |
1-core or 3-core |
25-800 |
15-49 |
18/30(36)kV |
1-core or 3-core |
35-630 |
23-49 |
26/35(40.5)kV |
1-core or 3-core |
50-800 |
31-57 |
Technical Data
Test item |
12/20(24)kV |
18/30(36)kV |
26/35(40.5)kV |
A.C. voltage withstand test |
No flashover, no breakdown at 54kV for 5min. |
No flashover, no breakdown at 81kV for 5min. |
No flashover, no breakdown at 117kV for 5min. |
Partial discharge test |
20kV, <10pC |
30kV, <10pC |
45kV, <10pC |
Heating cycles voltage test |
60 cycles at the temperature of 95-100°C, 30kV |
60 cycles at the temperature of 95-100°C, 45kV |
60 cycles at the temperature of 95-100°C, 65kV |
Impulse voltage withstand test at 95-100°C |
No flashover, no breakdown at 10 positive and 10 negative impulses at 125kV |
No flashover, no breakdown at 10 positive and 10 negative impulses at 170kV |
No flashover, no breakdown at 10 positive and 10 negative impulses at 200kV |
15min, A.C. voltage withstand test |
30kV, 15min. no flashover, no breakdown |
45kV, 15min. no flashover, no breakdown |
65kV, 15min.no flashover, no breakdown |