Anti tracking cable breakouts
Features |
Moulded anti-tracking cable breakout boots |
Operating temperature: -55~105ºC |
Insulation, protection,shield |
Shrink temperature: 120~140 ºC |
Life expectancy of 20 years at -55ºC to105ºC |
Shrink ratio:≥ 2:1 |
Red sealant liner |
Voltage class: 24~36 KV |
Flame retardant (optional ) |
|
Technical Data |
Property |
Test method |
Values |
Physical |
Tensile strength |
ASTM D2671 |
≥10 MPa |
|
Breakdown elongation |
ASTM D2671 |
≥350% |
Aging (136ºC /168hrs) |
Tensile strength |
ASTM D2671 |
≥8 MPa |
Breakdown elongation |
ASTM D2671 |
≥250% |
|
Water absorption |
ASTM D570 |
≤0.5% |
|
Density |
ASTM D2671 |
1.1~1.2 |
|
Thermal endurance |
IEC 216 |
-55~105ºC |
|
Low temperature flexibility(-55ºC/4hrs) |
ASTM D2671 |
No cracking |
|
Heat shock (200ºC/4hrs) |
ASTM D2671 |
No drop, No flow |
Electrical |
Volume resistivity |
ASTM D2671 |
≥1014 Ω.cm |
|
Dielectric strength |
ASTM D2671 |
≥20 KV/mm |
|
Anti-tracking |
ASTM 2303 |
No tracking |
3 cores breakouts are widely used in electric power industry to provide insulation with sealing over the cruth of multi-core cabcables. There are 3 clors: Red, black and mauve. Dia of body and finger is available. The elongation at breakis 300%, and longitudinal shrinkage is +-5%Property Typical Data
Hardness 80(shoea A)
Tensile strength 10mpa
Elongation at break 300%
Shrink temperature 120-140
Shrink ration(dia) 250%
Longitudinal shrinkage ± 5%