Cable jointing and termination kits of both heat and cold shrinkable type
1.20 years producing experience in heat shirnkable products, 8 years exporting experience
2. Stable quality and large stock, also pretty competitive price
3.4 voltage grade, 0.6/1KV, 8.7/15KV, 12/20KV, 26/35KV
4. All sets passed IEC60520 and JB8144 testing
All kinds of equipment are required for cable laying, connection and maintenance, including cable heads, splitters, connectors, etc. . Cable accessories not only need to have high quality and reliable performance, but also in strict accordance with cable specifications and specifications selection and use
Cold Shrink Cable Accessories:
1. cold shrinkable cable accessories adopt world renowned brand liquid/solid silicone rubber material. The products are with excellent insulation, anti-tracking, rebound resistance, heat/cold resistance, ozone resistance, anti-aging, and good dielectric properties, and can be used under various harsh conditions.
2. Geometric stress control method.
3. Standards compliance: IEC60502, GB/T12706.4, EN50180& EN50181(C type bushing)
4. Cold installation, easy and safe without using fire, just by pulling the spiral.
Technical Data:
Rated Voltage |
8.7/15(17.5)kV |
12/20(24)kV |
18/30(36)kV |
26/35(40.5)kV |
Running Temperature |
17.5kV |
24kV |
36kV |
40.5kV |
AC Withstand Voltage and DC Withstand Voltage |
39kV, 5min or 35kV, 15min, no flashover, no breakdown |
54kV,5min, or 48kV, 15min, no flashover, no breakdown |
81kV, 5min, or 72kV, 15min, no flashover, no breakdown |
117kV, 5min or 104kV, 15 min no flashover, no breakdown |
Partial Discharge |
15kV, PD≤5pC |
20kV, PD≤5pC |
30kV, PD≤5pC |
45kV, PD≤5pC |
Impulse Voltage Test |
95kV, ±10 times |
125kV, ±10 times |
170kV, ±10 times |
200kV, ±10 times |
Short Circuit Thermal Stability (Conductor) |
24kA, 2s twice, no visible damage |
25kA, 2s twice, no visible damage |
23kA, 2s twice, no visible damage |
25kA, 2s twice, no visible damage |
Short Circuit Dynamic Stability |
83kA, not less than 10ms, no visible damage |
63kA, not less than 10ms, no visible damage |
83kA, not less than 10ms, no visible damage |
88kA, not less than 10ms, no visible damage |
Constant Voltage Load Cycle |
apply voltage 1.25U0 to conductor and heat to(90-95)ºC heat for 5h and cool for 3h, total 3 times |
Salt Spray Test |
1.25U0 1000h, no flashover, no breakdown, trip not more than 3 times, no obvious damage |
Humidity Test |
1.25U0 300h, no flashover, no breakdown, trip not more than 3 times, no obvious damage |
Long-time Running Temperature |
-40ºC to 95ºC |
Short Circuit Temperature |
250ºC, lasting time less than 5s |
Cable Accessories Conductor Material |
copper, aluminum, copper&aluminum |