12/24KV heat shrinkable cable termination kits (WSY-24/3.1) for CU/XLPE/SWA/PVC Cable. We have 0.6/1KV low voltage and 8.7/15KV, 12/20KV and 18.7/35KV. single core, and 3 cores. We would like to receive your detaild cable cross section for sending you our samples for testing
Power Cable Termination Technology: Stress Cone
• Power Cable Termination Voltage Class(kV): ≤ 42
• Cable Shield Style: Copper wire, copper tape
• Number of Cores: 1, 3
• Application Type: Indoor
• Industry Standards: Design Specification GB/T 12706.4, IEC 60502-4
Test item |
12/20(24)kV |
18/30(36)kV |
26/35(40.5)kV |
A.C. voltage withstand test |
No flashover, no breakdown at 54kV for 5min. |
No flashover, no breakdown at 81kV for 5min. |
No flashover, no breakdown at 117kV for 5min. |
Partial discharge test |
20kV, <10pC |
30kV, <10pC |
45kV, <10pC |
Heating cycles voltage test |
60 cycles at the temperature of 95-100°C, 30kV |
60 cycles at the temperature of 95-100°C, 45kV |
60 cycles at the temperature of 95-100°C, 65kV |
Impulse voltage withstand test at 95-100°C |
No flashover, no breakdown at 10 positive and 10 negative impulses at 125kV |
No flashover, no breakdown at 10 positive and 10 negative impulses at 170kV |
No flashover, no breakdown at 10 positive and 10 negative impulses at 200kV |
15min, A.C. voltage withstand test |
30kV, 15min. no flashover, no breakdown |
45kV, 15min. no flashover, no breakdown |
65kV, 15min.no flashover, no breakdown |
Heat-shrinkable cable terminals
It commonly known as heat-shrinkable cable heads, are widely used on the terminals of cross-linked cables or oil-immersed cables with voltage levels of 35KV and below. Compared with the traditional cable accessories, the intermediate connection of the cable has the characteristics of small size, light weight, safety and reliability, and convenient installation.